the main and auxiliary machines in the refrigeration room were discovered. At the same time, an energy saving potential analysis was conducted for the existing system operation problems, and corresponding energy saving optimization control strategies were proposed. By adding a set of Internet of
Things intelligent control energy saving optimization control system to the refrigeration room, the comprehensive energy saving rate of the renovated refrigeration room system was 19.1%, providing an efficient and feasible solution for energy saving and consumption reduction of the air conditioning system
in existing buildings.
Key words: Refrigeration Room; Energy Saving; Building; Internet of Things Intelligent Control
0 引言
清华大学建筑节能研究中心发布的《中国建筑
节能年度发展研究报告(2021)》显示,中国建筑运
行能耗占全社会总能耗的23%[1]
。建筑能耗和碳排
放主要来源于用电最多的季节性空调,空调能耗是
建筑运行能源消耗中最主要的组成部分,约占建筑
运行能耗的50%左右,超过了照明、电梯、办公设备
的总能耗[2-3]
。制冷机房作为空调系统的源头,它的
节能与否是判断建筑是否节能的关键。因此,制冷
机房节能的意义非常重大,诊断与分析制冷机房的
节能问题也显得尤为重要与迫切。
1 工程概况
工程为上海某 5A 甲级办公楼,总建筑面积
达 2.8万m2
,地上18层,地下1层,标准层建筑面积
1 639 m2
,标准层层高3.3 m,物业管理方式为第三
方公司管理。办公楼主要能源消耗类型为电力、天
然气。
大厦中央空调制冷机房设置于 B1 层,空调冷
源为3台螺杆式水冷机组,辅机包括4台一次冷冻
泵、4台二次冷冻泵、4台冷却泵、3台冷却塔。制冷
机房设备清单见表1所示。
2 制冷机房系统运行现状
针对项目制冷机房部分安装物联网数据采集
系统,并于9月25日正式上线,现截取采集周期内
数据汇总如表2所示。
2.1 冷机运行规律
冷机本地模式下开关记录如表3。
可知:为迅速使大楼降温,工作日早晨通常先
开启两台冷机1~3 h,随后切换为单机运行;除加班
等特殊情况外,冷机每天6:30左右开启,全天运行
表1 制冷机房设备清单
设备类型
螺杆式冷机组
一次冷冻泵
二次冷冻泵
冷却泵
冷却塔
数量(台)
3
4
4
4
3
功率(kW)
264.5
15
18.5
37
15
备注
已配置变频器
双速电机
表2 物联网数据采集情况表
采集周期
9月25日-10月11日
采集天数(天)
17
采集频率(min/次)
3
采集点位数量
42
数据类型
末端温湿度,水系统温度、压力,各用电
设备实时电流,功率等
采集数据量(万)
34.3
上海某大厦制冷机房系统节能诊断分析
1669