昆山科诺泰电气设备有限公司
用
户
操
作
使
用
说
明
书
KBC-800-65 工业机柜空调说明书
昆山科诺泰电气设备有限公司
用
户
操
作
使
用
说
明
书
KBC-800-65 工业机柜空调说明书
目 录
1. 安全注意事项·······················································································1
2. 安装要求 ·····························································································1
2-1 安装位置·························································································2
2-2 安装方法·························································································3
2-3 电器配线························································································6
2-4 机器排水·························································································6
3. 启动与运转···························································································6
3-1 运行前后注意事项···········································································6
3-2 机器操作说明··················································································7
4. 维护与保养·························································································10
4-1 定期清洁·······················································································10
4-2 长时间停用时注意··········································································10
5. 故障排除·····························································································10
附录一······································································································11
附录二······································································································11
1. 安全注意事项
⑴ 当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册
中所提到的注意事项,以避免出现意外情况;
⑵ 请勿用湿手操作,以免引起触电;
⑶ 当需要保养或维护时,请先切断所有电源以免引起触电事故;
⑷ 空调器上不易放置任何物品,以免滑落造成人员伤害;
⑸ 当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受
伤或机器损坏;
⑹ 本机器不宜露天放置以免雨水进入机体内,并且也不适宜于安装在振动较
大或者移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司
咨询;
⑺ 本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请
致电本公司咨询;
⑻ 禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员
咨询,以防意外发生。
2. 安装要求
本空调器为侧挂式系列,侧挂式(图一),为使机组能在理想的状况下工作,
在安装上请注意以下要求:
图一 侧挂式
空调器
电
控
箱
回风
(热)
出风
(冷)
2-1 安装位置
⑴ 空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、
可燃性气体、粉尘类气体、油污类气体等品质较差的空气中;如果确实需要
在粉尘及油污等品质较差的环境中安装空调器,则一定要每天做好空调器的
清洁和保养工作。
⑵ 空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会
排出热量,如果空调器周围排气不畅很容易导致其周围的温度升高,这将影
响空调器的制冷效果。见图三,空调器进、排风口离墙面的间距应大于
500mm;
⑶ 空调器周围请勿放置杂物,以保持空气畅通流通;
⑷ 本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影
响冷却效果。
⑸ 请安装本空调器于周围温度在 45℃以下的范围之内高温系列 55℃以下;
⑹ 本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必
须保持垂直,其倾斜角不大于 5°如图四所示;
⑺ 控制箱内正对出风口的电器元件与出风口的最小距离应大于 200mm,因
距离太近电器元件表面易产生水膜现象,从而导致电器故障的发生。若无法
避免,请在电器元件前增加一块隔热材料;并且箱内出风口四周的电器元件
与出风口应保持一定的距离,以便减小箱内空气的流通阻力。
⑻ 当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便
箱体内空气的温、湿度能控制在较为理想的状态下。
图三
电
控
箱
冷气机
图 四
错 误 正 确 错 误 正 确
2-2 安装方法
⑴ 当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设
备长期放在露天场所;
⑵ 为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上,请
勿采用风管的形式进行送风,如若确实需要采用风管送风,请先咨询本公司
技术工程师;
⑶ 空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免
造成人员受伤及设备损坏,当安装在电气柜门上时,最好该扇箱门能固定不
动,当需要打开时请先确认好加在门上的重量不会使整个电气柜倾倒;
⑷ 电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参
见图五;
⑸ 箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划
伤机组;
⑹ 当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有
可能导致机器掉落而损坏;
⑺具体的安装方式如下:
1.冷出风挡板安装示意图:(如不安装出风口有凝结水风险)
C. 用升降车安全的把空调器从安装面安
装到电控箱上,注意安装时把电线先从
电线孔伸入到电箱内,再在电控箱内侧
螺栓上垫好垫圈,并用螺帽拧紧。
d. 在机组底部出水口连接好排水管,
用抱箍固定好,另一端请引入排水沟
或蓄水桶内,检测电源是否与机组匹
配,然后接上电源即可开机使用。
b. 卸下机组背后安装螺钉上
的螺帽与垫圈,控制好螺栓
的伸出长度约 15mm
排水管
蓄水桶
螺帽与垫片
进风口
送风口
a.首先在电控柜上开好与
所选空调相对应的安装孔
电
控
箱
电
控
箱
机柜开孔
电源线 机柜侧面
或门
2-3 电器配线:
⑴ 机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或过
低,若所提供的电压在额定值±10%以内,本机组可正常使用;
经常在超过额定电压值的环境中使用,将会大大缩短压缩机和其他电气设备及元件的使用
寿命,此类损坏不属于我公司包修范围,只负责收费维修。请用户千万注意
⑵ 空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一根电
源线,当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;
⑶ 在机组的电器回路上请自行安装断路器或漏电保护装置;
⑷ 请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电源超
出负载,引发事故。
2-4 机器排水:
本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这部
分水气就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请注意
以下几点:
⑴ 请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连接处;
⑵ 根据实际情况排水软管长度适当即可,过长部分请切除;
⑶ 排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内产生
淤水严重时产生外溢,引起空调器或者电气柜故障。
3. 启动与运行
3-1 运行前后注意事项
⑴ 启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插上电
源开始工作;
⑵ 当在运转中需重新启动空调器时,请间隔 3 分钟以上,倘若频繁启动且间隔时间过短会
引起机器损伤;
⑶ 当空调器倾斜时请勿开启,避免漏水、触电等情况发生;
⑷ 空调器在出厂时温度点已经设定好为 30℃,若需重新设定时请控制在允许范围之内设
定,以免引起机器运行不正常;如果空调器有加热功能,出厂时设置为 5℃
⑸ 当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并请专业人员进
行检查维修。
3-2 机器操作说明:
系统参数设置界面进入:
系统参数设置
输入密码:
长按〖P〗键 3 秒,数码管显示“---0”( 设置密码为 1111,直接进入参数设置);
按〖▼〗键循环选择密码当前位,按〖▲〗键设置当前位密码值;
按〖S〗键确认(密码正确显示“F00”,错误退出参数设置);
注:出厂初始密码:1111
参数设置:
按〖▲〗或〖▼〗键选择参数代码;
按〖S〗键选择该参数的设定值,再按〖▲〗或〖▼〗键进行参数设置;
按〖S〗键回到参数代码选择,以此循环设置;
设置完成长按〖P〗键 3 秒退出设置(此次参数设置被保存);
注:若 30 秒内无按键操作自动退出设置,此次参数不保存(控制器仍按原来的参数运行)
5.1 显示符号说明
图标 功能 亮 灭 闪烁
压缩机控制 启动 停止 正在延时保护
风机控制 启动 停止
5.2 显示代码说明
显示代码 说明
E1 柜内温度传感器故障(短路或断路)
E2 蒸发器温度传感器未接或故障(短路或断路)
HP 压缩机高压告警
SHP 压缩机高压停机保护(1 小时内发生 4 次报警)
LoF 缺氟报警
SLoF 缺氟停机保护(1 小时内发生 3 次缺氟保护)
Hi 高温报警
Lo 低温报警
FrE 蒸发器冻结提示
Fd 压缩机强制开启提示
参数代码表
代码 功能 范围 说明 出厂默
认
F00 温度设定值 0~50.0℃ 30
F01 温控回差 1~15 5
F02 冻结保护温度 -10 ~ 10 -1
F03 冻结恢复温度 -10 ~ 10 5
F04 柜内温度校正 -10.0 ~ 10.0 0
F05 蒸发器温度校
正
-10.0 ~ 10.0 0
F06 压缩机延时保
护时间
0~9 3
F07 高温报警回差 0~50 0:禁止 0
F08 低温报警回差 0~50 0:禁止 0
F20 风机运行模式 0~1 0:温控模式;
1:常开模式
0
F21 风机启动温度 0~50.0℃ 26
F22 风机温控回差 1~15 2
F30 压缩机高压告
警输入
0~2 0:禁止;
1:常闭报警;
2:常开报警;
02
F31 缺氟保护 0~1 0: 禁止;
1: 开启;
0
F32 密码 0~9999 0:关闭密码功能 1111
制冷控制
柜内温度≥温度设定值+温控回差,且满足压缩机延时保护时间,开启制冷;
柜内温度≤温度设定值,关闭制冷;
压缩机强制启动
长按〖▲〗键 5 秒(数码管交替闪烁显示 Fd 和柜内温度),强制开启压缩机,1 小时后自
动退出;
强制开启状态长按〖▲〗键 5 秒可立即退出;
风机控制
常开模式,风机始终开启;
温控模式:
当柜内温度 ≥风机启动温度,且风机停机≧1 分钟,风机开启;
当柜内温度 ≤风机启动温度 - 风机温控回差,且风机开机≧1 分钟,风机关闭;
注:1. 柜内温度 ≤风机启动温度,压缩机开(包括强制启动),风机开,压缩机关,风
机延时 120 秒后关闭;
2. 蒸发器冻结保护期间风机开启;
蒸发器冻结保护
压缩机连续工作 3 分钟后;
蒸发器温度≤冻结保护温度, 且持续时间≥5 秒,关闭压缩机(数码管交替闪烁显示 FrE
和柜内温度);
蒸发器温度≥冻结恢复温度,系统恢复正常制冷;
蒸发器温度查询
按〖S〗键查询蒸发器温度(闪烁显示 3 秒钟后恢复);
超温报警
柜内温度≥温度设定值+温控回差+高温报警回差,且持续时间≥5 秒,高温报警(数码管
交替闪烁显示 Hi 和柜内温度);
柜内温度≤温度设定值-低温报警回差,且持续时间≥5 秒, 低温报警(数码管交替闪烁
显示 Lo 和柜内温度);
温度校正功能
柜内温度测量值可以通过 F04 进行校正;
蒸发器温度测量值可以通过 F05 进行校正;
温度传感器故障报警
柜内温度传感器故障(短路或断路):
进入定时制冷控制,数码管闪烁显示 E1,关闭缺氟保护功能(蒸发器冻结保护功能开启);
*定时制冷控制:30 分钟为一运行周期,制冷 15 分钟,关闭 15 分钟;
蒸发器温度传感器故障(短路或断路):
蒸发器温度传感器未接或故障,温度查询显示 E2,关闭蒸发器冻结保护功能及缺氟保护功
能;
压缩机高压报警
压缩机高压报警信号有效,且持续时间≥5 秒,停压缩机,数码管交替闪烁显示 HP 和柜
内温度。高压报警信号恢复正常,控制器恢复正常制冷控制;
如果 1 小时内发生 4 次报警,压缩机将一直停机保护,数码管交替闪烁显示 SHP 和柜内
温度,关电源重新上电解除故障报警;
缺氟保护
压缩机连续工作 5 分钟后,若柜内温度-蒸发器传感器温度<5 度,进入缺氟保护,强制
关闭压缩机,数码管交替闪烁显示 LoF 和柜内温度,压缩机延时保护后自动开启压缩机制
冷;
如果 1 小时内发生 3 次缺氟保护,压缩机将一直停机保护,数码管交替闪烁显示 SLoF 和
柜内温度,关电源重新上电解除故障报警;
恢复到出厂设置
长按〖▼〗键 5 秒,显示 UnL,再按两次〖▼〗键,恢复出厂默认
4.维护与保养
请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空气过
滤网和冷凝器。对于机器上安装的是尼龙滤网的可直接从侧面拔出
4-1 定期清洁
本机的滤网材质为尼龙滤网,可直接从网罩上面拉出,用洗涤水清洗干净,
并晾干后按原样装回,一般每周需清洗一次;
⑵ 请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲
洗空调器,以防发生触电事故;
4-2 长时间停用时注意
⑴ 请切断电源,以防意外;
⑵ 清理冷凝器、过滤网及内部油污;
⑶ 请对机器采取防尘措施,延长机器使用寿命。
4. 故障排除
故障状况 1 电源接通后,室内、室外风机不运转
可能原因
※保险丝熔断
※停电或无电源
状况排除
※更换保险丝
※检查电源状况
故障状况 2 在运行中突然停机,电控箱内温度高于设定点温度两度以上
可能原因
※环境温度过高,导致压缩机热保护
※过滤网堵塞或者冷凝器过脏,导致压缩机热保护
状况排除
※改善周边环境,使散热畅通
※对过滤器及冷凝器进行清洗
故障状况 3 机器正常运转,却不制冷
可能原因
※压缩机损坏
※制冷系统泄露
※机组蒸发器大面积结霜
状况排除
※更换压缩机,重新抽真空充注制冷剂
※查出泄露处,并重新抽真空加制冷剂
※立即停机,把设定温度调高到 35℃,十分钟后重新开机
◇若上述措施均不能排除故障,请致电本公司咨询!
附录 1:产品技术参数
型号:KBC-800-65 工作电源: 交流 220V ±10% 频率 50Hz ±4%
运行电流: <2.4A 功 率: 450W
制冷剂: R134a 制冷量: 800W 充注量:150g
防护等级:内循环:IP34 外循环:IP54
允许机柜内温度设定范围:25--38℃(出厂设定 30℃)
允许使用环境温度范围:-25--65℃
循环风量: 内循环:230m ³/h 外循环 290m ³/h 噪音:55dB
附录 2:电气原理图
室内风机 室外风机 压缩机
M1 M2 M3
C2 C3
L
N
PE
t℃温控器
KBC-800-65
主回路电路图控制回
温
控
器
昆 山 科 诺 泰 电 气 设 备 有 限 公 司
地址:苏州市昆山市张浦镇垌坵路 199 号
联系电话:18121419046