多联制冷机组说明书
51
liquid refrigerant raises from low pressure side of charging ways to supplement
refrigerants. 除了对已确定的系统可进行称量加注外,确定制冷剂充注量的常用方法之一是观察液体
管道视液镜中制冷剂的流动情况。当液体流动清晰可见时,就可认为制冷剂已正确加注。出现
气泡通常说明制冷剂不足,但也可能是视镜前的液管存在缩放部分或冷凝压力的快速变化使制
冷剂压力下降。因此视液镜可作为一种确定制冷剂加注量的一个有效依据。
In addition to the determined system has been weighted and supplement
refrigerant, commonly used method of filling quantity of fluid is used to watch flow
condition of refrigerant in the level glass of pipeline. When the liquid flows clearly, we
can think refrigerants has correctly supplement. Exsiting air bubbles that usually indicates
insufficient refrigerants, but may also existence of scaling part in the liquid pipe before
level glass or refrigerant pressure drop because of condensing pressure changes quickly. Therefore level glass can be used as a kind of determination of an effective filling station. (三)、应保持清洁干燥,定期清扫风冷冷凝器翅片的灰尘及油污等杂物及传热管内侧的污
垢。
Should maintain clean and dry, regularly clean air-cooled condenser the dust and finned heat
and debris to grease the dirt. (四)、查电控线头及其它部件是否有松动现象,如遇异常应及时维修和更换,检查前务必
切断电源。Check whether the components and other electronic thread is loose, if exsiting any
abnormal phenomenon, should be timely maintenance and replacement, before inspection make
sure cut off supply power . (五)、多联机组停机时,应重点检查每组电磁阀是否关闭严,如果关闭不严将会对压缩机
造成重大的损害 When multi-connecting unit stops, we should check every group
electromagnetic valve whether closed tightly , if not closed will cause major compressor damage
(六)、机组长期停机的操作步骤 Operating steps for unit long time closing down