TECHNICAL DATAElectrical CharacteristicsType FMS-12W PV2/1Input 2 stringOutput 1 stringMaximum Voltage DC 1000VMAX DC Short Circuit Current Per Input (Isc) 15A(Changeable)Maximum Current Output 32AEnvironmentOperating Temperature -25° C~ + 55° CHumidity 99%Altitude 2000Mlnstallation Wall MountingEnclosure FMS-12WMeterial Tpye Stainless steel/Stainless steel spray / Cold rolled steel sprayDegree of Protection IP66Dimension(WxHxD) 300x350x140mm(1.2mm/1.2mm)Cable input entry Pg9 Cable Gland 4-8mm2 ... [收起]
[展开]
俊朗外贸元器件选型
粉丝: {{bookData.followerCount}}
文本内容
第51页

TECHNICAL DATA

Electrical Characteristics

Type FMS-12W PV2/1

Input 2 string

Output 1 string

Maximum Voltage DC 1000V

MAX DC Short Circuit Current Per

Input (Isc) 15A(Changeable)

Maximum Current Output 32A

Environment

Operating Temperature -25° C~ + 55° C

Humidity 99%

Altitude 2000M

lnstallation Wall Mounting

Enclosure FMS-12W

Meterial Tpye Stainless steel/Stainless steel spray / Cold rolled steel spray

Degree of Protection IP66

Dimension(WxHxD) 300x350x140mm(1.2mm/1.2mm)

Cable input entry Pg9 Cable Gland 4-8mm2

/ 4mm2

MC4 connector

Output Cable Gland Pg21 Cable Gland

DC Isolator Switch

Rated Insulation VOltage(Ui) DC 1000V

Rated Current(le) 32A

Category DC-PV2, DC-PV1, DC-21 B

Standard Compliance with IEC60947-3

Certification TUV, CE, CB, SAA, ROHS

DC Surge Protection Device

Max Operation Voltage(Ucpv) DC 1000V

Standard Compliance with EN 61643-31 Type 2

Maximum Discharge Current 40KA

Certification TUV, CE,CB, ROHS

DC Fuse Holder SFPV-25BX

LED lndicator Yes

Rated Working Voltage DC 1000V

Fuse Link 10x38mm 15A

Certification TUV, CE, CB, ROHS

48 47/48 Let the electricity run out to.....

第52页

FMS-18W PV4/1B

Metal PV DC

combiner box

FMS-18W PV4/1B Metal PV DC combiner box is suitable for inverter (MAX input

voltage DC1000V, single MPPT inverter). Box body is made of stainless steel,

stainless steel spray, cold rolled steel spray, with test for fire retardant, temperature

rise, anti impact, anti ultraviolet, and other testing. IP65 protection grade.

Design and configuration strictly accordance with the “Technical specification for

photovoltaic junction equipment” CGC/GF 037:2014. Provide users with a safe, brief,

beautiful and applicable photovoltaic system products.

Application:

49/50 Let the electricity run out to..... 49

第53页

TECHNICAL DATA

Electrical Characteristics

Type FMS-18W PV4/1B

Input 4 string

Output 1 string

Maximum Voltage DC 1000V

MAX DC Short Circuit Current Per

Input (Isc) 15A(Changeable)

Maximum Current Output 63A

Environment

Operating Temperature -25℃ ~ + 55℃

Humidity 99%

Altitude 2000M

lnstallation Wall Mounting

Enclosure FMS-18W

Meterial Tpye Stainless steel/Stainless steel spray / Cold rolled steel spray

Degree of Protection IP66

Dimension(WxHxD) 300x400x140mm(1.2mm/1.2mm)

Cable input entry Pg9 Cable Gland 4-8mm2

/ 4mm2

MC4 connector

Output Cable Gland Pg21 Cable Gland

DC MCB JLB1Z-63/4P

Rated Insulation VOltage(Ui) DC 1000V

Rated Current(le) 63A

Category DC-21B

Standard Compliance with IEC60947-2

Certification CB,ROHS

DC Surge Protection Device JLD-PV/3

Max Operation Voltage(Ucpv) DC 1000V

Standard Compliance with EN 61643-31 Type 2

Maximum Discharge Current 40KA

Certification TUV, CE,CB, ROHS

DC Fuse Holder SFPV-25BX

LED lndicator Yes

Rated Working Voltage DC 1000V

Fuse Link 10x38mm 15A

Certification TUV, CE, CB, ROHS

50 49/50 Let the electricity run out to.....

第54页

FMS-24W PV6/2

Metal PV DC

combiner box

FMS-24W PV6/2 Metal PV DC combiner box is suitable for inverter (MAX input

voltage DC1000V, double MPPT inverter). Box body is made of stainless steel,

stainless steel spray, cold rolled steel spray, with test for fire retardant, temperature

rise, anti impact, anti ultraviolet, and other testing. IP65 protection grade.

Design and configuration strictly accordance with the “Technical specification for

photovoltaic junction equipment” CGC/GF 037:2014. Provide users with a safe, brief,

beautiful and applicable photovoltaic system products.

Application:

51/52 Let the electricity run out to..... 51

第55页

TECHNICAL DATA

Electrical Characteristics

Type FMS-24W PV6/2

Input 6 string

Output 2 string

Maximum Voltage DC 1000V

MAX DC Short Circuit Current Per

Input (Isc) 15A(Changeable)

Maximum Current Output 32A

Environment

Operating Temperature -25℃ ~ + 55℃

Humidity 99%

Altitude 2000M

lnstallation Wall Mounting

Enclosure FMS-24W

Meterial Tpye Stainless steel/Stainless steel spray / Cold rolled steel spray

Degree of Protection IP66

Dimension(WxHxD) 460x350x140mm(1.2mm/1.2mm)

Cable input entry Pg9 Cable Gland 4-8mm2

/ 4mm2

MC4 connector

Output Cable Gland Pg21 Cable Gland

DC Isolator Switch L2-32

Rated Insulation VOltage(Ui) DC 1000V

Rated Current(le) 32A

Category DC-PV2, DC-PV1, DC-21 B

Standard Compliance with IEC60947-3

Certification TUV, CE, CB, SAA, ROHS

DC Surge Protection Device JLD-PV/2

Max Operation Voltage(Ucpv) DC 1000V

Standard Compliance with EN 61643-31 Type 2

Maximum Discharge Current 40KA

Certification TUV, CE,CB, ROHS

DC Fuse Holder SFPV-25BX

LED lndicator Yes

Rated Working Voltage DC 1000V

Fuse Link 10x38mm 15A

Certification TUV, CE, CB, ROHS

52 51/52 Let the electricity run out to.....

第56页

run out to.....

Let the electricity

53

第57页

AC Mini circuit breaker series(MCB)

AC Mini isolator switch series

AC Residual current circuit breaker series(RCCB)

AC Surge protection device series(SPD)

AC Molded case circuit breaker series (MCCB)

AC Molded case circuit breaker with residual current

protection series

AC Contactor Series

AC Dual power automatic transfer switch series (ATS)

55/

69/

73/

83/

85/

89/

91/

93/

Solar PV AC

products

53/54 Let the electricity run out to.....

第58页

JLB1-63

Mini circuit breaker with H-breaking

capacity( Icu=6kA)

JLB1-63 miniature circuit breaker with high-breaking capacity is mainly used for

protection against overload and short circuit under AC 50Hz/60Hz, rated voltage

230V/400V and rated current from 6A to 63A. It also can be used for non-frequent

on-and-off switching operation under normal circumstance.

Application:

55/56 Let the electricity run out to..... 55

第59页

• In compliance with IEC/EN60898-1

• Maximum connecting ability of 25sqmm, wiring torque 2.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Overload and short circuit protection.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique design looks elegant.

TECHNICAL DATA

Product advantages

Type JLB1-63

Rated current(A) 6, 10, 16, 20, 25, 32, 40, 50, 63

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated breaking capacity(kA) 6

Electrical life 10000

Mechanical life 20000

Protection degree IP20

Thermo-magnetic release characteristic C,D

Instantaneous protection current range C:5In<I<10In ; D:10In<I<20In

Standard IEC60898-1,GB/T10963.1

As needed

Installation dimensions(mm)

56 55/56 Let the electricity run out to.....

第60页

JLB2-63

Mini circuit breaker with H-breaking

capacity( Icu=6kA)

JLB2-63 miniature circuit breaker with high-breaking capacity are applicable for places with

AC 50Hz or 60Hz, rated voltage 230/400V, and rated current of 6A-63A. It is mainly used

for overload and short-circuit protection of lighting, power distribution lines and equipment

in office buildings, residences and similar buildings. It can also be used for infrequent line

transfer under normal conditions.

Application:

57/58 Let the electricity run out to..... 57

第61页

As needed

• In compliance with IEC/EN60898-1

• Maximum connecting ability of 25sqmm, wiring torque 2.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Overload and short circuit protection.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique bi-color design.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type JLB2-63

Rated current(A) 6, 10, 16, 20, 25, 32, 40, 50, 63

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated breaking capacity(kA) 6

Electrical life 10000

Mechanical life 20000

Protection degree IP20

Thermo-magnetic release characteristic C,D

Instantaneous protection current range C:5In<I<10In ; D:10In<I<20In

Standard IEC60898-1,GB/T10963.1

58 57/58 Let the electricity run out to.....

第62页

JLB3-63

Mini circuit breaker with H-breaking

capacity( Icu=6kA)

JLB3-63 miniature circuit breaker with high-breaking capacity are applicable for places with

AC 50Hz or 60Hz, rated voltage 230/400V, and rated current of 6A-63A. It is mainly used

for overload and short-circuit protection of lighting, power distribution lines and equipment

in office buildings, residences and similar buildings. It can also be used for infrequent line

transfer under normal conditions.

Application:

59/60 Let the electricity run out to..... 59

第63页

As needed

• In compliance with IEC/EN60898-1

• Maximum connecting ability of 25sqmm, wiring torque 2.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Overload and short circuit protection.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique design.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type JLB3-63

Rated current(A) 6, 10, 16, 20, 25, 32, 40, 50, 63

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated breaking capacity(kA) 6

Electrical life 10000

Mechanical life 20000

Protection degree IP20

Thermo-magnetic release characteristic C,D

Instantaneous protection current range C:5In<I<10In ; D:10In<I<20In

Standard IEC60898-1,GB/T10963.1

60 59/60 Let the electricity run out to.....

第64页

JLB5-63

Mini circuit breaker with H-breaking

capacity( Icu=6kA)

JLB5-63 miniature circuit breaker with high-breaking capacity are applicable for places with

AC 50Hz or 60Hz, rated voltage 230/400V, and rated current of 6A-63A. It is mainly used

for overload and short-circuit protection of lighting, power distribution lines and equipment

in office buildings, residences and similar buildings. It can also be used for infrequent line

transfer under normal conditions.

Application:

61/62 Let the electricity run out to..... 61

第65页

As needed

• In compliance with IEC/EN60898-1

• Maximum connecting ability of 25sqmm, wiring torque 2.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Overload and short circuit protection.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique design.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type JLB5-63

Rated current(A) 6, 10, 16, 20, 25, 32, 40, 50, 63

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated breaking capacity(kA) 6

Electrical life 10000

Mechanical life 20000

Protection degree IP20

Thermo-magnetic release characteristic C,D

Instantaneous protection current range C:5In<I<10In ; D:10In<I<20In

Standard IEC60898-1,GB/T10963.1

62 61/62 Let the electricity run out to.....

第66页

JLB6-63

Mini circuit breaker with H-breaking

capacity( Icu=6kA)

JLB6-63 miniature circuit breaker with high-breaking capacity are applicable for places with

AC 50Hz or 60Hz, rated voltage 230/400V, and rated current of 6A-63A. It is mainly used

for overload and short-circuit protection of lighting, power distribution lines and equipment

in office buildings, residences and similar buildings. It can also be used for infrequent line

transfer under normal conditions.

Application:

63/64 Let the electricity run out to..... 63

第67页

As needed

• In compliance with IEC/EN60898-1

• Maximum connecting ability of 25sqmm, wiring torque 2.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Overload and short circuit protection.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique design.

• Transparent cover designed to carry label.

• Error proof terminal more easy for wiring and has the advantage of higher safety.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type JLB6-63

Rated current(A) 6, 10, 16, 20, 25, 32, 40, 50, 63

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated breaking capacity(kA) 6

Electrical life 10000

Mechanical life 20000

Protection degree IP20

Thermo-magnetic release characteristic C,D

Instantaneous protection current range C:5In<I<10In ; D:10In<I<20In

Standard IEC60898-1,GB/T10963.1

64 63/64 Let the electricity run out to.....

第68页

YHB3-80(M/H)

Mini circuit breaker with H-breaking

capacity( Icu=6kA/10kA)

YHB3-80 miniature circuit breaker with high-breaking capacity is mainly used for protection

against overload and short circuit under AC 50Hz/60Hz, rated voltage 230V/400V and rated

current from 1A to 80A. It also can be used for non-frequent on-and-off switching operation

under normal circumstance.

Application:

65/66 Let the electricity run out to..... 65

第69页

As needed

• In compliance with IEC/EN60898-1.

• Maximum connecting ability of 25sqmm, wiring torque 2.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Overload and short circuit protection.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Error proof terminal more easy for wiring and has the advantage of higher safety.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique design looks elegant.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type YHB3-80(M/H)

Rated current(A) 6, 10, 16, 20, 25, 32, 40, 50, 63,80

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated breaking capacity(kA) 6/10

Electrical life 10000

Mechanical life 20000

Protection degree IP20

Thermo-magnetic release characteristic C,D

Instantaneous protection current range C:5In<I<10In ; D:10In<I<20In

Standard IEC60898-1,GB/T10963.1

66 65/66 Let the electricity run out to.....

第70页

JLB67-125(H)

Mini circuit breaker with H-breaking

capacity( Icu=6kA/10kA)

JLB67-125 miniature circuit breaker with high-breaking capacity are applicable for places

with AC 50Hz or 60Hz, rated voltage of 230/400V, and rated current of 63A-125A. It is

mainly used for overload and short-circuit protection of lighting, power distribution lines

and equipment in office buildings, residences and similar buildings. It can also be used for

infrequent line transfer under normal conditions.

Application:

67/68 Let the electricity run out to..... 67

第71页

• In compliance with IEC/EN60898-1.

• Maximum connecting ability of 25sqmm, wiring torque 2.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Overload and short circuit protection.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Error proof terminal more easy for wiring and has the advantage of higher safety.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique design looks elegant.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type JLB67-125(H)

Rated current(A) 63, 80,100,125

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated breaking capacity(kA) 6/10

Electrical life 10000

Mechanical life 20000

Protection degree IP20

Thermo-magnetic release characteristic C,D

Instantaneous protection current range C:5In<I<10In ; D:10In<I<20In

Standard IEC60898-1,GB/T10963.1

68 67/68 Let the electricity run out to.....

第72页

JLHL-125

AC mini isolator switch

JLHL-125 mini isolator switch has high stability, as the main switch in the terminal

combination of electrical appliances, suitable for the power distribution and control loop of

AC 50/60Hz, rated voltage below 415V, rated current up to 125A for isolating. It can also be

used to control motors, small power appliances and lighting, widely used in industrial and

mining enterprises, high buildings, commercial and family places etc.

Application:

69/70 Let the electricity run out to..... 69

第73页

• In compliance with IEC/EN60947-3

• Maximum connecting ability of 35/50sqmm, wiring torque 3.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Isolating function.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique Bi-color design.

• Long service life.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type JLHL-125

Rated current(A) 20, 25, 32, 40, 63, 80,100,125

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated short time withstand current Icw 12In 1s

Rated short time breaking capacity Icm 20In 0.05s

Usage category AC-22A

Operation frequency 120 times/h

Electrical life 1500

Mechanical life 8500

Protection degree IP20

lnstallation mode Embedded type din rail mounting

Connection type The terminal block or busbar with clamp

Connection capability Allow the wire under 50mm2

to connect with

Tightening torque values 3.5N•m

70 69/70 Let the electricity run out to.....

第74页

JLH2-125

AC mini isolator swith

JLH2-125 mini isolator switch has high stability, as the main switch in the terminal

combination of electrical appliances, suitable for the power distribution and control loop of

AC 50/60Hz, rated voltage below 415V, rated current up to 125A for isolating. It can also be

used to control motors, small power appliances and lighting, widely used in industrial and

mining enterprises, high buildings, commercial and family places etc.

Application:

71/72 Let the electricity run out to..... 71

第75页

• In compliance with IEC/EN60947-3

• Maximum connecting ability of 35/50sqmm, wiring torque 3.5Nm, applicable to a variety of installing equipment.

• Protection class:IP20

• Isolating function.

• Lighting for power distribution, and motor protection.

• Visualization window.Red and green indicator lights, power on and off at a glance, to avoid wrong operation.

• PA66 (nylon), flame retardant material shell.

• Material in line with the European ROHS certification standards.

• Widened handle improving operation comfort and easy.

• Magnetic blown arc extinguishing device, improve product arc extinguishing ability to ensure the improvement of

breaking capacity.

• Silver alloy contact tip for higher breaking capacity and lower arc created.

• Novel and unique Bi-color design.

• Long service life.

TECHNICAL DATA

Product advantages

Installation dimensions(mm)

Type JLH2-125

Rated current(A) 20, 25, 32, 40, 63, 80,100,125

Pole(P) 1, 2, 3, 4

Rated voltage(V) 1P, 2P 3P, 4P

AC 230/400 AC 400

Rated frequency(Hz) 50/60Hz

Insulation voltage Ui(V) 500

Rated short time withstand current Icw 12In 1s

Rated short time breaking capacity Icm 20In 0.05s

Usage category AC-22A

Operation frequency 120 times/h

Electrical life 1500

Mechanical life 8500

Protection degree IP20

lnstallation mode Embedded type din rail mounting

Connection type The terminal block or busbar with clamp

Connection capability Allow the wire under 50mm2

to connect with

Tightening torque values 3.5N•m

72 71/72 Let the electricity run out to.....

第76页

JLB1L-63

AC Residual current circuit breaker with over

current protection (RCBO).

• This product meet the shandard of IEC/EN61009-1

• Maximum connecting ability of 16/25mm2

,wiring torque 2.5/3.0Nm, applicable to a

variety of installing equipments,wiring stronger.

• Protection class:1P20

JLB1L-63 Series residual currrent circuit breaker is used for protection against electrical

leakage, overload,short circuit,over voltage in the circuit of 50/60Hz,rated voltage

230/400V, rated current up to 63A.

When people come across the electric shock or the leakage current of the electrical

network exceeds the fixed value,this product can cut off the fault current in one second

so as to protect personal safety and prevent accident on equipments caused by residual

current from happening.lt also can be used to protect circuit against short circuit and

overloading,and used for infrequent on -and-off switching operation under normal

circumstance.lt is mainly applied in architectural lighting and power distribution system

protection.

Application:

73/74 Let the electricity run out to..... 73

第77页

TECHNICAL DATA

Installation dimensions(mm)

Frame rated

current Inm A

Rated current

In A Poles Rated voltage

V

Breaking capacity of rated

short-circuit Instantaneous

release type lcs(A) COS Φ

63 6,10,16,20,25,

32,40,50,63

1P+N, 2P,

3P, 3P+N, 4P 230 4500 0.65-0.70 C

In(A) IΔn(A) Residual current (in) is equal to the breaking time (s)

at the following corresponding value

6-63 0.03

IΔn 2IΔn 250mA

0.1 0.05 0.04

Rated current ln(A) ln≤6 6<ln≤6 13<ln≤20 20<ln≤25 25<ln≤32 32<ln≤50

Nominal cross-section

of wire(mm2

) 1 1.5 2.5 4 6 10

Ambient

temperature Initial status Test current Test time Expected result Note

30±2℃

Cold position 1.13ln t ≥1h Non-release -

Carried out

immediately

after previous test

1.45ln t<1h Release -

Cold position 2.55ln 1 s<t<60s

(In≤32A) Release Current smoothly

rises to specified

Cold position 2.55ln value within 5s 1s<t<120s

(ln>32A) Release

-5~+40℃

Cold position 3ln t≤0.1s Non-release Type B

Cold position 5ln t<0.1s Release Type B

Cold position 5ln t≥0.1s Non-release Type C

Cold position 10ln t<0.1s Release Type C

Cold position 10ln t≥0.1s Non-release Type D

Cold position 20ln t<0.1s Release Type D

1 15)3&\"%

1

1

1 / 1 / 15)3&\"%



















74 73/74 Let the electricity run out to.....

第78页

JLB67RN-125

AC Residual current circuit breaker with over

current protection (RCBO)

• This product meet the shandard of IEC/EN60947-2 & IEC/EN61009-1

• Maximum connecting ability of 35mm2

,wiring torque 3.5Nm, applicable to a variety of

installing equipments.wiring stronger.

• Protection class:IP20

JLB67RN-125 Series residual currrent circuit breaker is used for protection against

electrical leakage, overload, short circuit, over voltage in the circuit of 50/60Hz,rated

voltage 230/400V, rated current up to 125A.When people come across the electric shock or

the leakage current of the electrical network exceeds the fixed value.This product can cut

off the fault current in one second so as to protect personal safety and prevent accident

on equipments caused by residual current from happening.It also can be used to protect

circuit against short circuit and overloading,and used for infrequent on-and-off switching

operation under the normal circumstance.lt is mainly applied in architectural lighting and

power distribution system protection.

Application:

75/76 Let the electricity run out to..... 75

第79页

Installation dimensions(mm)

Standard IEC/EN 60947-2 IEC/EN 61009-1

Electrical

features

Poles 1P+N, 2P, 3P, 3P+N, 4P

Rated current In A 63, 80, 100, 125

Rated voltage Ue V 230/400

Insulation voltage Ui V 400

Rated frequency Hz 50/60

Rated sensitivity lΔn A 0.03 0.1 0.3

Rated residual making and breaking capacity

IΔm A lcu=6000 lcs=6000

Break time under lΔn S 0.1

Rated impulse withstand voltage (1.2/50)

Uimp V 6000

Dielectric lest voltage at and ind.Freq.for 1

min kV 2.5

Pollution degree 2

Electrical life and Mechanical life 4000

Mechanical

features

Thermo-magnetic release characteristic 8-12 In C

Fault current indicator ℃ Yes

Protection degree ℃ IP20

Ambient temperature(with daily

average≤35℃ ℃ -5~+40

Storage temperature ℃ -25~+70

Combination

with

accessories

Terminal connection type Cable/U-type busbar/Pin -type busbar

Terminal size top/bottom for cable mm2

AWG 25 18-3

Tightening torque mounting N*m

In-lbs.

2.5 22 On DIN rail EN 60715 (35mm) by

means of fast clip device

Connection From top and bottom

POLES 1P+N 2P 3P 3P+N 4P

L(mm) 54 81 108 108 135

H(mm) 73.5 78.5 78.5 78.5 78.5

\"TOFFEFE

TECHNICAL DATA

76 75/76 Let the electricity run out to.....

第80页

YHB2LE-80

AC Residual current circuit

breaker(Electronic type)

• Bilateral busbar wiring capabilities to adapt to the wider use of premises.

• Maximum connecting ability of 35mm2

,wiring torque 3.5Nm, applicable to a variety of

installing equipments, wiring stronger.

• Protection class:IP20

YHB2LE-80 Series electronic type residual current circuit breaker is suitable to the circuit

ofAC50/60Hz,rated voltage 230V for 2poles and 400V for 4 poles, and rated current up to

80A.When people come across the electric shock or the leakage current of the electrical

network exceeds the fixed value, this product can cut off the fault current in short period

so as to protect persons and the equipments, It also can be used in the infrequent starting

of the circuit and motors. The circuit breaker is suitable to industry, commerce, high-rise

building, household and other kinds of places.This product meets the standard of IEC/

EN61008-1 .It has the following features:

Application:

77/78 Let the electricity run out to..... 77

第81页

Installation dimensions(mm)

Pole number 2P 4P

Shelf rating current A 80

Electrical properties

Rated working voltage Ue VAC 230 400

Rated current In A 6、10、16、20、25、32、40、50、63、80

Rated residual action current 1Δn mA 10、15、30、50、100、200

Leakage tripping type A / AC

Rated Insulation Voltage U i V 500

Rated Impulse Voltage Breakdown Type Limit Uimp kV 4

Split type M H

Breaking capacity operating Icu kA 6000 10000

Breaking capacity force Ics kA

Curve type B、C、D

Release type Thermomagnetic

Service life

(O~CO)

Machincal Actualaverage 20000

Standard value 8500

Electrical Actualaverage 10000

Standard value 1500

Control and indication

Auxiliary contact □

Alarm contact □

Shunt release □

Under release □

Voltage release □

Connection and installation

Protection grade All sides P40

Connection port IP20

Handle lock ON/OFF Position

Connection ability mm 2 1~35

Use ambient temperature ℃ -30~

+70

Humidity and heat resistance 2

Altitude m ≤2000

Relative humidity of air +20℃ ≤W95%+40℃ ≤50%

Pollution grade 3

Installation environment Without significant vibration and impact

Installation category III

Installation mode DIN Standard guide rail

Shape dimensions(mm)

Width * Height * Depth

a 35.2 70.4

b 82 82

c 72.6 72.6

Weight g 210.5 210.5

F

TECHNICAL DATA

78 77/78 Let the electricity run out to.....

第82页

JXL8-63

AC Residual current circuit

breaker(Electromagnetic type)

• In compliance with IEC/EN61008-1

• Bilateral busbar wiring capabilities to adapt to the wider use of premises.

• Maximum connecting ability of 35mm2

,wiring torque 3.5Nm, applicable to a variety

ofinstalling equipments, wiring stronger.

• Protection class:IP20

JXL8-63 Series electromagnetic type residual current circuit breaker is a kind of protective

device against residual current, is suitable to the circuit of AC 50/60Hz, rated voltage up to

400V, rated current to 63A.lt is mainly used to protect human safety from electrical shock

and prevent fire disaster caused by residual current due to damaged equipment.lt also can

be used in the infrequent on -and-off switching operation under normal case. This circuit

breaker is mainly applied to industry, mine, building, household, hotel and other similar

locations.

Application:

79/80 Let the electricity run out to..... 79

第83页

Installation dimensions(mm)

• Classification

o According to number of poles 2 poles, 4 poles

o According to type of instantaneous release AC type, A type

• Mechanical/Electric lifetime (times)

-Electric lifetime (times):2000, cosΦ=0.85~9

-Mechanical life (times):2000

-Operating frequency: 120times/hour

• Rated insulation impulse withstand voltage

When poles are connected to each other, the peak value of the impulse with stand-voltage between each poles and the neutral pole is 6000V;

When each pole is connected to the neutral pole, the peak value of the impulse withstand-voltage between poles and the metal support is 8000V;

• The product can withstand peak impulse current of 200A and peak surge over-voltage 2.5Un, and under such a situation, the protection switch

can act correctly without mis-operation.

TECHNICAL DATA

Poles 2P, 4P

Rated voltage Un (V) 2P/230, 4P/400

Rated current In (A) 25,40,63

Case class rated current lnm(A) 63

Rated residual action current IΔn(A) 0.03,0.1,0.3

Rated residual non-action current IΔno(A) 0.015,0.05,0.15

Rated making/breaking capacity IΔm(A) ln=25,40/500,ln=63/630

Rated limited short-circuit current Icu(A) 6000

Rated limited residual short-circuit current IΔc(A) 6000

Rated residual current breaking time See table 2

In (A) IΔn(A) Residual current (In) is equal to the switch-off time (s) at the following

corresponding value

16,25,40,63 0.03,0.1,0.3

IΔn(A) 2IΔn(A) 5IΔn(A) 10A, 20A, 50A, 100A, 200A, 500A

63 0.1 0.08 0.04

a: IΔnS0.03A, 0.25A can Instead of 5IΔn

80 79/80 Let the electricity run out to.....

第84页

JL11-63

AC Residual current circuit

breaker(Electromagnetic type)

• In compliance with IEC/EN61008-1

• Bilateral busbar wiring capabilities to adapt to the wider use of premises.

• Maximum connecting ability of 35mm2

,wiring torque 3.5Nm, applicable to a variety

ofinstalling equipments, wiring stronger.

• Protection class:IP20

JL11-63 Series electromagnetic type residual current circuit breaker is a kind of protective

device against residual current, is suitable to the circuit of AC 50/60Hz, rated voltage up to

400V, rated current to 63A.lt is mainly used to protect human safety from electrical shock

and prevent fire disaster caused by residual current due to damaged equipment.lt also can

be used in the infrequent on -and-off switching operation under normal case. This circuit

breaker is mainly applied to industry, mine, building, household, hotel and other similar

locations.

Application:

81/82 Let the electricity run out to..... 81

第85页

Installation dimensions(mm)

• Classification

o According to number of poles 2 poles, 4 poles

o According to type of instantaneous release AC type, A type

• Mechanical/Electric lifetime (times)

-Electric lifetime (times):2000, cosΦ=0.85~9

-Mechanical life (times):2000

-Operating frequency: 120times/hour

• Rated insulation impulse withstand voltage

When poles are connected to each other, the peak value of the impulse with stand-voltage between each poles and the neutral pole is 6000V;

When each pole is connected to the neutral pole, the peak value of the impulse withstand-voltage between poles and the metal support is 8000V;

• The product can withstand peak impulse current of 200A and peak surge over-voltage 2.5Un, and under such a situation, the protection switch

can act correctly without mis-operation.

TECHNICAL DATA

In (A) IΔn(A) Residual current (In) is equal to the switch-off time (s) at the following

corresponding value

16,25,40,63 0.03,0.1,0.3 IAn(A) 2IAn(A) 5IAn(A) 10A, 20A, 50A, 100A, 200A, 500A

63 0.1 0.08 0.04

a: IΔnS0.03A, 0.25A can Instead of 5IΔn

Poles 2P, 4P

Rated voltage Un (V) 2P/230, 4P/400

Rated current In (A) 25,40,63

Case class rated current lnm(A) 63

Rated residual action current IΔn(A) 0.03,0.1,0.3

Rated residual non-action current IΔno(A) 0.015,0.05,0.15

Rated making/breaking capacity IΔm(A) ln=25,40/500,ln=63/630

Rated limited short-circuit current Icu(A) 6000

Rated limited residual short-circuit current IΔc(A) 6000

Rated residual current breaking time See table 2

82 81/82 Let the electricity run out to.....

第86页

JLD

AC Surge protection device

series(SPD)

• Status indicator

• Low residual, short response time

• Thermal disconnect device.

• Core components are strictly screened, stable performance and reliable operation.

• Using the latest arc extinguishing technology to avoid fire completely

• Module is designed and installed conveniently and can be replaced directly.

JLD Series T2 surge protective device is suitable for power distribution and controlling

system under the circuit of AC50Hz/60Hz, rated voltage 230/400V. It is used to protect

all of the electrical equipment in the power system from lightning and against transient

over voltage, release surge power to the ground so that protect circuits and equipment. In

compliance with IEC/EN61643-11.

Application:

83/84 Let the electricity run out to..... 83

第87页

TECHNICAL DATA

Model JLD-40 JLD-80 JLD-120

Nominal voltage Un(VAC.) 385V

Max.continuous operating voltage Uc(VAC) 385V

Nominal discharge current ln(8/20μs) 20KA 40KA 60KA

Max.discharge current lmax(8/20μs) 40KA 80KA 120KA

Voltage protection level Up ≤1.8kV ≤2.4kV ≤2.5kV

SPD Type T2

AC system TN

Pole 1P, 2P, 3P, 4P

Protection mode(s) L/PE

Technology MOV(Metal Oxide Varistors)

Plugable Yes

Mounting 35mm DIN rail

Housing material PA66(nylon),flame retardant

Operating temperature -40℃ to +70℃

Pemissible operating humidity 5%...95%

Altitude ≤3000m

Protection rating IP20(built-in)

Operating state/fault indication Green/Red

Remote Signaling Optional

Standdards compliance IEC 61643-11/EN 61643-11

84 83/84 Let the electricity run out to.....

第88页

JLM6

AC Molded case circuit breaker

(MCCB)

JLM6 series molded case circuit breaker is one of our new type products developed and

manufactured by adopting international advanced technology. This series of product has a

small volume, high breaking capacity, stable performance, complete accessories, convenient

and other features, widely used in AC 50Hz/60Hz rated operating current from 10A to 1600A

distribution network, mainly used to allocate power, and line power supply equipment.

Equipped with the protection devices for overload, short circuit and under voltage. It can be

also used as an infrequent change over and start of the motors.

Application:

85/86 Let the electricity run out to..... 85

第89页

TECHNICAL DATA

Model JLM6-63 JLM6-125 JLM6-250 JLM6-400 JLM6-630 JLM6-800 JLM6-

1600

Poles 3 4 2 3 4 2 3 4 3 4 3 4 3 4 3

Rated Current(A)

10 16 20

25 32 40

50 63

16 20 25 32

40 50 63 80

100 125

100 125 140

160 180 200

225 250

225 250

315 350

400

400 500

630

630 700

800

1000

1250

1600

Rated lnsulation

Voltage 690 800 1000

Rated lmpulse

Withstand Voltage 6000 8000 1200

Rated Working Voltage 400 AC400/690

Breaking Type - L M H L M H L M H M H

Rated

Limited

Short-circuit

Breaking

Capacity

400V 50 35 50 85 35 65 85 50 65 100 75 100 100 85

690V - - - 25 - - 25 - - 30 - 30 - -

Rated

Working

Short-circuit

Breaking

Capacity lcs

(kA)

400V 35 25 35 50 25 50 65 35 50 65 50 65 75 65

690V - - - 15 - - 15 - - 20 - 20 - -

Arcing Distance 50 100

Service Life

(O-C)

Times/h 60 60 20

Electrical

life 8000 7000 500

Mechanical

life 20000 10000 2500

86 85/86 Let the electricity run out to.....

第90页

HGM

AC Molded case

circuit breaker

HGM series molded case circuit breaker is one of our new design product and obtained good

design award, developed and manufactured by adopting international advanced technology.

This series of product has a small volume, high breaking capacity, stable performance, more

safe and convenient to install complete accessories, and other features, widely used in AC

50Hz/60Hz rated operating current from 16A to 250A distribution network, mainly used to

allocate power, and line power supply equipment. Equipped with the protection devices for

overload, short circuit and under voltage. It can be also used as an infrequent change over

and start of the motors.

Application:

87/88 Let the electricity run out to..... 87

第91页

TECHNICAL DATA

Model HGM100 HGM125 HGM160 HGM250

Frame 100 125 160 250

Poles 3,4 3,4 3,4 3,4

Rated Current(A) 100 16,20,25,32,40,50,63,75,

80,100,125 100,125,150,160 100,125,150,160

175,200,225,250

Rated

Limited

Shortcircuit

Breaking

Capacity

[Icu]

(kA rms)

Breaking type E H L H L H L

AC660/690V 2.5 8 10 8 10 8 10

AC480/500V 7.5 26 35 26 35 26 35

AC440/460 V 16 38 55 38 55 38 55

AC380/415 V 16 38 55 38 55 38 55

AC220/240V 35 85 100 85 100 85 100

DC250V(2P) 5 20 30 20 30 20 30

Rated Working Short-circuit

Breaking Capacity lcs (kA) 100 100 100 100 100 100 100

Service

life

Mechanical life 30,000 30,000 25,000 25,000

Electrical life 10,000 10,000 10,000 10,000

Rated lnsulation Voltage 1,000V

Rated Working Voltage 690V

Rated lmpulse Withstand Voltage 8kV

Protection function Overload, short circuit, Instantaneous protection

Isolating Function Yes

Category A

Pollution rating 3

Standard GB 14048.2

IEC 60947-2

88 87/88 Let the electricity run out to.....

第92页

JLM6L

AC Molded case circuit breaker with

residual current protection

JLM6L series molded case circuit breaker with residual current protection, rated working

voltage is up to 400V, suitable for the distribution circuit with AC 50Hz, rated working current

up to 800A, as leakage protection. It can be used to prevent equipment from insulation

damage, fire hazard due to ground fault. Also be used to distribute electric energy and protect

circuits, power supplies and protect electrical equipment from overload, short circuit, under

voltage and other faults. It can also protect motors from infrequent starting, overload and short

circuit.

The circuit breaker has the characteristics of small size, high breaking capacity, short

arc flashover and adjustable residual operating current. It is an ideal product for power

distribution.

This product cannot be reversed into the line, only 1, 3, 5 can be connected to the power line,

and 2, 4, 6 can be connected to the load line. This product complies with IEC60947-2, GB/

T14048.2 standards. The product has an isolation function.

Application:

89/90 Let the electricity run out to..... 89

第93页

TECHNICAL DATA

Model JLM6L-125 JLM6L-250 JLM6L-400 JLM6L-630,800

Frame 125 250 400 800

Poles 2 3 4 2 3 4 3 4 3 4

Rated Current(A) 16,20,25,32,40,50,

63,80,100,125

125,140,160,180,

200,225,250

225,250,315,

350,400

400,500,630,

700,800

Rated lnsulation Voltage(V) AC800

Rated Working Voltage(V) AC400

Rated lmpulse Withstand

Voltage(V) 8000 8000 8000 8000

Arcing Distance(mm) 50 50 100 100

Rated Limited

Short-circuit

Breaking Capacity

Icu(kA)

AC400V 35 50 65 65

Rated Working

Short-circuit

Breaking Capacity

lcs (kA)

AC400V 22 35 40 42

Rated residual short circuit

breaking capacity making

capacity IΔmkA

8.75 12.5 16.25 16.25

Rated residual

operating current

IΔn(mA)

Non- delay

type

30/100/200/

300/500

30/100/200/

300/500

30/100/200/

300/500

30/100/200

/300/500

Delay type 100/200/300/500 100/200/300/500 100/200/300/500 100/200/300/500

Rated residual non-working

current.(mA) 1/2 IΔn 1/2 IΔn 1/2 IΔn 1/2 IΔn

Service life(O-C)

Times/h 60 60 60 60

Electrical life 8000 8000 7000 7000

Mechanical life 20000 20000 10000 10000

Residual current breaking

time IΔn 2 IΔn 5 IΔn 2 IΔn

Max breaking

time(s)

Non- delay

type 0.2 0.1 0.04

Delay type 0.5/1.15/2.15 0.35/1/2 0.25/09/1.9

90 89/90 Let the electricity run out to.....

第94页

JX2

AC Contactor

JX2 series AC contactor is suitable for using in the circuits up to the rated voltage 660V AC

50Hz or 60Hz, rated current up to 95A, for making, breaking,frequently starting & controlling

the AC motor. Combined with the auxiliary contact block, timer delay & machine-interlocking

device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta

starter. With the thermal relay, it is combined into the electromagnetic starter. The contactor is

produced according to IEC60947-5-1, VDE0660 & BS5452

Application:

91/92 Let the electricity run out to..... 91

第95页

Standard Control Circuit Voltages

Specifications

Volts 24 42 48 110 220/230 230 240

50Hz B5 D5 E5 F5 M5 P5 U5

60Hz B6 D6 E6 F6 M6 - U6

50/60Hz B7 D7 E7 F7 M7 P7 U7

Volts 380/400 400 415 440 500 660

50Hz Q5 V5 N5 R5 S5 Y5

60Hz Q6 - - R6 - -

50/60Hz Q7 V7 N7 R7 - -

Type CJX2-9 CJX2-12 CJX2-18 CJX2-25 CJX2-32 CJX2-40 CJX2-50 CJX2-65 CJX2-80 CJX2-D95

Rated

working

current

(A)

AC-3 9 12 18 25 32 40 50 65 80 95

AC-4 3.5 5 7.7 8.5 12 18.5 24 28 37 44

AC-3

capacity

of

phase

220/230V 2.2 3 4 5.5 7.5 11 15 18.5 22 25

380/440V 4 5.5 7.5 11 15 18.5 22 30 37 45

415V 4 5.5 9 11 15 22 25 37 45 45

440V 4 5.5 9 11 15 22 30 37 45 45

500V 5.5 7.5 10 15 18.5 22 30 37 55 55

660/690V 5.5 7.5 10 15 18.5 30 33 37 45 45

Rated heat

current (A) 20 20 32 40 50 60 80 80 125 125

AC-4×104 20 20-15 20-7 15-7 15-7 10-7 7 7 7-5 7-5

AC-3×104 200 200 200 200 200 200 200 160 160 160

Mechanical

life×104 2000 2000 2000 2000 2000 2000 2000 2000 1000 1000

Number of the

contact

3P+NO 3P+NC+NO

3P+NC 3P+NC+NO

92 91/92 Let the electricity run out to.....

第96页

JLQ2

AC Dual power automatic transfer

switch(ATS)

JLQ2 series Dual power automatic transfer switch mainly used for distribution or electromotor

network, rated voltage 400V, rated current 16A-3200A.

Main power and standby power or mutual standby power changeover system or city power

and generator group overload switch-over. At the same time, it can operated under infrequent

on and off circuit act as disconnector.

Widely used at the field of important power supply site, which transport, distribution power

supply system and automation system. For fire protection, hospital, bank, building, etc, where

doesn't allow power off.

Application:

93/94 Let the electricity run out to..... 93

第97页

Note: The weight in the table are for reference only.

Standard Control Circuit Voltages

Type JLQ2

Frame current(A) 100 250 630 1600 3200

Rated working

current (In) 16 20 25 32 40 50 63 80 100 125 160 200 225 250 315 350 400 500 630 800 1000 1250 1600 2000 2500 3200

Rated insulation v

atage (Ui) 690V 800V

Rated Impulse

Withstand Voltage

(U imp)

8KV 8KV

Rated Working

Voltage (Uw) AC400V AC400V

Usage Category AC-33B AC-33iB

Rated limited short

circuit current 8KA 17KA 26KA 67.5KA

Rated short-time

withstand current 5kA/30ms 10kA/60ms 12.6kA/60ms 32kA/60ms

Transfer time 2.5s 0.6s 1.2s 1.8s 2.4s

Control power

voltage DC24V,48V,110V,AC220V

Rated

frequency

voltage

20W

325W 355W 400W 440W 600W

Normal 62W 74W 90W 98W 120W

Weight(kg) 4pole 3.4 6.0 7.6 15.8 16.8 36 36 37 38.6 55 61 67

94 93/94 Let the electricity run out to.....

第98页

JULAN ELECTRIC CO.,LTD

ADD:No. 2, Zhengshun West Road, Xiangyang

Industrial Zone, Liushi Town,Yueqing City,Zhejiang Province,China.

TEl:+86-577-6161 6621

PC :325604

https://julanele.en.alibaba.com/ E-catalog https

百万用户使用云展网进行翻页电子书制作,只要您有文档,即可一键上传,自动生成链接和二维码(独立电子书),支持分享到微信和网站!
收藏
转发
下载
免费制作
其他案例
更多案例
免费制作
x
{{item.desc}}
下载
{{item.title}}
{{toast}}